Equipment monitoring infrared temperature sensor
The FLIR A310 is a fixed-mount infrared camera that can be installed almost anywhere to monitor your critical equipment and other valuable assets. This camera protects your plant and measures temperature differences to assess the criticality of a given situation. It helps you identify problems ahead of time to avoid their development as a costly failure, preventing downtime while ensuring worker safety.
Monitor your critical equipment
Excellent image quality
The FLIR A310 is equipped with a 320 x 240 pixel vanadium oxide (VOx) microbolometer that detects temperature differences as small as 50 mK.
Industrial agreement
Compatible with Ethernet/IP and Modbus TCP protocols for sharing analysis and alarm results to programmable logic controllers; with digital input/output for alarm and external device control.
Built-in analysis and alarm
The A310 features point, zone temperature and temperature differential measurements and can perform alarms based on analysis, internal temperature or digital inputs.
The company sells infrared thermal imaging cameras, infrared thermal imagers, Philip thermal imaging cameras and other products, welcome to inquire.
Alarm function arbitrarily selected measurement function, digital input, camera temperature and timer have 6 automatic alarm functions
Alarm output digital output, log, save image, file send (ftp), email (SMTP), notification
Base mounting 2 x M4 threaded mounting holes (3 sides)
Detector type focal plane array ( FPA), uncooled microbolometer
Temperature difference calculates the temperature difference between each temperature measurement and the reference temperature
Focal length 18 mm
Housing material aluminum
Infrared resolution 320 × 240 pixels
Set command date /time, temperature (°C/°F)
Dimensions (length × width × height) 170 × 70 × 70 mm
Wavelength range 7.5-13 μm
Tripod mount UNC 1/4"-20 (3 sides)
Zoom 1–8 times continuous, digital, image interpolation zoom
Content carton, infrared camera (with lens), Ethernet cable, FLIR Tools download card, power cord, cable - flexible copper, power supply, printed document, user documentation CD-ROM, utility CD-ROM
Measurement and analysis
Accuracy ±2°C or ±2% of reading
Regional temperature measurement 10 input boxes, including limit value/limit small value/average/position
External optical lens and window correction automatically, based on lens /window transmission and temperature input values
1 isotherm , including above and below the isotherm / interval
Measurement correction global and single target parameters
Measurement Options Measurement Mask Filter Call Response: File Send ( ftp), Email (SMTP)
Object temperature range –20 to +120°C 0 to +350°C
Optics transmission correction automatically, based on signals from internal sensors
Reference temperature manual setting, or according to measurement
Reflective apparent temperature correction automatically, based on reflected temperature input value
Point thermometer 10.0
Thermal sensitivity / NETD 0.05 ° C @ +30 ° C / 50 mK
Imaging and optics
Palette palette (black and white, black and white, iron red, iridescent)
Detector pixel pitch 25μm
Detection time constant is typically 12ms
Aperture number 1.3
Field of view ( FOV) 25° × 18.8°
Focusing automatically or manually (built-in motor)
Image frequency 9 Hz
Lens recognition automatically
Extreme small focal length 0.4 m
Spatial resolution ( IFOV) 1.36 mrad
Video Standard CVBS (ITU-R-BT.470 PAL/SMPTE 170M NTSC)
Storage medium
File format standard JPEG, including 16-bit temperature measurement data
power supply
External power connector type 2 pin screw terminal
External power management 12/24 VDC, relative power limit is 24 W
Voltage tolerance range 10–30 VDC
Environmental parameters
Atmospheric transfer correction is automatic, based on input values of distance, atmospheric temperature and relative humidity
Electromagnetic compatibility ( EMC) EN 61000-6-2 (anti-interference) EN 61000-6-3 (radiation resistance) FCC 47 CFR Part 15 Class B (radiation resistance)
Emissivity correction ranging from 0.01 to 1.0
Package IP 66 (IEC 60529)
Humidity (work and storage) IEC 60068-2-30/24 hours, 95% relative humidity, +25°C to +40°C
Operating temperature range -15 ° C to +50 ° C
Impact resistant 25 g (IEC 60068-2-27)
Storage temperature range -40°C to +70°C
Anti-vibration 2 g (IEC 60068-2-6)
Connection and communication
Digital input /output connector type 6-pin screw terminal
Digital input / output insulation voltage 500 VRMS
Digital input /output supply voltage 6–24 VDC, maximum 200 mA
Digital input purpose image mark (start /stop/general), input to external device (programmatically read)
Digital input 2 optically isolated, 10–30 VDC
The digital output is output to an external device according to the alarm (programmed)
Digital output 2 optically isolated, ON = power supply (maximum 100 mA), OFF = disconnected
Ethernet control, measurement results and images
Ethernet communication based on TCP/IP sockets, FLIR proprietary
Ethernet connector type RJ-45
Ethernet image stream at 4.5 Hz with 16 bits of 320 x 240 pixels - radiation
Ethernet power supply, Power over Ethernet, PoE IEEE 802.3af class 0 power supply standard
Ethernet protocol Ethernet/IP, Modbus TCP, TCP, UDP, SNTP, RTSP, RTP, HTTP, ICMP, IGMP, ftp, SMTP, SMB (CIFS), DHCP, MDNS (Bonjour), uPnP
Ethernet standard IEEE 802.3
Ethernet type 100 Mbps
Ethernet video stream MPEG-4, ISO/IEC 14496-1 MPEG-4 ASP@L5
Storage media built-in image storage memory card
Video output composite video output, compatible with PAL and NTSC
Video connector type standard BNC interface