Banner
Equipment monitoring infrared temperature sensor

Equipment monitoring infrared temperature sensor

Product Details


The FLIR A310 is a fixed-mount infrared camera that can be installed almost anywhere to monitor your critical equipment and other valuable assets. This camera protects your plant and measures temperature differences to assess the criticality of a given situation. It helps you identify problems ahead of time to avoid their development as a costly failure, preventing downtime while ensuring worker safety.

Monitor your critical equipment

Excellent image quality

The FLIR A310 is equipped with a 320 x 240 pixel vanadium oxide (VOx) microbolometer that detects temperature differences as small as 50 mK.

Industrial agreement

Compatible with Ethernet/IP and Modbus TCP protocols for sharing analysis and alarm results to programmable logic controllers; with digital input/output for alarm and external device control.

Built-in analysis and alarm

The A310 features point, zone temperature and temperature differential measurements and can perform alarms based on analysis, internal temperature or digital inputs.

The company sells infrared thermal imaging cameras, infrared thermal imagers, Philip thermal imaging cameras and other products, welcome to inquire.





Alarm function arbitrarily selected measurement function, digital input, camera temperature and timer have 6 automatic alarm functions

Alarm output digital output, log, save image, file send (ftp), email (SMTP), notification

Base mounting 2 x M4 threaded mounting holes (3 sides)

Detector type focal plane array ( FPA), uncooled microbolometer

Temperature difference calculates the temperature difference between each temperature measurement and the reference temperature

Focal length 18 mm

Housing material aluminum

Infrared resolution 320 × 240 pixels

Set command date /time, temperature (°C/°F)

Dimensions (length × width × height) 170 × 70 × 70 mm

Wavelength range 7.5-13 μm

Tripod mount UNC 1/4"-20 (3 sides)

Zoom 1–8 times continuous, digital, image interpolation zoom

Content carton, infrared camera (with lens), Ethernet cable, FLIR Tools download card, power cord, cable - flexible copper, power supply, printed document, user documentation CD-ROM, utility CD-ROM

Measurement and analysis

 

Accuracy ±2°C or ±2% of reading

Regional temperature measurement 10 input boxes, including limit value/limit small value/average/position

External optical lens and window correction automatically, based on lens /window transmission and temperature input values

1 isotherm , including above and below the isotherm / interval

Measurement correction global and single target parameters

Measurement Options Measurement Mask Filter Call Response: File Send ( ftp), Email (SMTP)

Object temperature range –20 to +120°C 0 to +350°C

Optics transmission correction automatically, based on signals from internal sensors

Reference temperature manual setting, or according to measurement

Reflective apparent temperature correction automatically, based on reflected temperature input value

Point thermometer 10.0

Thermal sensitivity / NETD 0.05 ° C @ +30 ° C / 50 mK

Imaging and optics

 

Palette palette (black and white, black and white, iron red, iridescent)

Detector pixel pitch 25μm

Detection time constant is typically 12ms

Aperture number 1.3

Field of view ( FOV) 25° × 18.8°

Focusing automatically or manually (built-in motor)

Image frequency 9 Hz

Lens recognition automatically

Extreme small focal length 0.4 m

Spatial resolution ( IFOV) 1.36 mrad

Video Standard CVBS (ITU-R-BT.470 PAL/SMPTE 170M NTSC)

Storage medium

 

File format standard JPEG, including 16-bit temperature measurement data

power supply

 

External power connector type 2 pin screw terminal

External power management 12/24 VDC, relative power limit is 24 W

Voltage tolerance range 10–30 VDC

Environmental parameters

 

Atmospheric transfer correction is automatic, based on input values of distance, atmospheric temperature and relative humidity

Electromagnetic compatibility ( EMC) EN 61000-6-2 (anti-interference) EN 61000-6-3 (radiation resistance) FCC 47 CFR Part 15 Class B (radiation resistance)

Emissivity correction ranging from 0.01 to 1.0

Package IP 66 (IEC 60529)

Humidity (work and storage) IEC 60068-2-30/24 hours, 95% relative humidity, +25°C to +40°C

Operating temperature range -15 ° C to +50 ° C

Impact resistant 25 g (IEC 60068-2-27)

Storage temperature range -40°C to +70°C

Anti-vibration 2 g (IEC 60068-2-6)

Connection and communication

 

Digital input /output connector type 6-pin screw terminal

Digital input / output insulation voltage 500 VRMS

Digital input /output supply voltage 6–24 VDC, maximum 200 mA

Digital input purpose image mark (start /stop/general), input to external device (programmatically read)

Digital input 2 optically isolated, 10–30 VDC

The digital output is output to an external device according to the alarm (programmed)

Digital output 2 optically isolated, ON = power supply (maximum 100 mA), OFF = disconnected

Ethernet control, measurement results and images

Ethernet communication based on TCP/IP sockets, FLIR proprietary

Ethernet connector type RJ-45

Ethernet image stream at 4.5 Hz with 16 bits of 320 x 240 pixels - radiation

Ethernet power supply, Power over Ethernet, PoE IEEE 802.3af class 0 power supply standard

Ethernet protocol Ethernet/IP, Modbus TCP, TCP, UDP, SNTP, RTSP, RTP, HTTP, ICMP, IGMP, ftp, SMTP, SMB (CIFS), DHCP, MDNS (Bonjour), uPnP

Ethernet standard IEEE 802.3

Ethernet type 100 Mbps

Ethernet video stream MPEG-4, ISO/IEC 14496-1 MPEG-4 ASP@L5

Storage media built-in image storage memory card

Video output composite video output, compatible with PAL and NTSC

Video connector type standard BNC interface


Inquiry